Author Archive
Deadtime versus Lag
The dynamic response of self-regulating processes can be described reasonably accurately with a simple model consisting of process gain, deadtime and lag (a.k.a. time constant). The process gain describes how much the process responds to a change in controller output, while the deadtime and time constant describes how quickly the process responds.
Note: Lag is a phenomenon and time constant is its measurement in time. But these two terms are often used interchangeably.
Although the deadtime and time constant both describe aspects of the process’ dynamic response, there are several fundamental differences between how deadtime and time constant affects a control loop. The first difference is that deadtime describes how long it takes a process to begin responding to a change in controller output, while the time constant describes how fast the process responds once it has begun moving.
Measuring the Deadtime and Time Constant of a Process
Let’s begin with the measurement of deadtime and time constant of a self-regulating process. Typically, one will place the controller in manual control mode, wait for the process variable to settle down, and then make a step change of a few percent in the controller output. At first the process variable does nothing (deadtime) and then it begins changing (time constant) until finally it settles out at a new level.
To measure the deadtime and time constant, draw a horizontal line at the same level as the original process variable. We’ll call this the baseline. Then find the maximum vertical slope of the process variable response curve. Draw a line tangential to the maximum slope all the way to cross the baseline. We’ll call this crossing the intersection.
– The process deadtime is measured along the time axis as the time spanned between the step change in controller output and the intersection.
Next, measure the total change in process variable. Then find the point on the process response curve where the process variable has changed by 0.63 of the total change in process variable. We’ll call this point P63.
– The process time constant is measured along the time axis as the time spanned between the intersection (described previously) and P63.
Deadtime versus Time Constant
We can draw a chart with a continuum of deadtime through time constant (see figure below). Processes with dynamics consisting of pure deadtime will be on the left and pure lag (time constant) on the right. In the middle the process deadtime will equal its time constant.
We’ll find that flow loops and liquid pressure loops fall just about in the middle of the continuum, because their deadtime and time constant are almost equal. Gas pressure and temperature loops will be located more toward the right – they are lag (time constant) dominant. Serpentine channels in water treatment plants and conveyors with downstream mass meters will appear on the left side – they are deadtime dominant.
Level loops should actually be treated differently because the are modeled without a time constant, but they can be approximated on the continuum by placing them all the way to the right, as if they have infinitely long time constants.
The ratio of deadtime to time constant affects the usefulness of derivative control, the tuning rules we use, the controllability of the process, and the shortest possible loop settling time.
Controller Modes
The derivative control mode works well where process variables continue to move in the same direction for some time, i.e. lag-dominant processes. Derivative control does not work well on processes where the process variable changes sporadically – typically processes with relatively short time constants, located in the middle and to the left on the continuum.
Applicability of Tuning Rules
Most tuning rules will work on lag-dominant processes. However, the Ziegler-Nichols rules have only a narrow range of applicability. Lambda tuning rules apply to a broader spectrum of processes, while Cohen-Coon has the widest coverage. The Deadtime tuning rule, applies to processes on the left, as its name implies.
Controllability
Lag-dominant loops are easier to control than deadtime-dominant loops. Operators find that lag-dominant processes respond much more intuitively than deadtime-dominant processes and are easier to control in manual mode.
Loop Settling Time
When tuning a loop for the shortest possible settling time, one finds that there is a minimum limit on settling time. If you tune the controller any tighter, the loop will begin oscillating, thereby increasing the settling time. The minimum settling time depends mostly on the deadtime in a control loop, and will be between two and four times the length of the deadtime. The ratio of time constant to deadtime determines where the minimum settling time falls between two and four times the process deadtime.
Stay tuned!
Jacques Smuts – Author of the book Process Control for Practitioners